preloader
mail@uselogic.ru  +7(495) 374 68 44 Заказать звонок

Область применения

Numerous CPUs with differing performance ranges are available for SIMATIC S7-400:

  • CPU 412-1, CPU 412-2 und CPU 412-2 PN:
    For smaller plants in the mid-performance range.
  • CPU 414-2, CPU 414-3, CPU 414-3 PN/DP:
    For medium-sized plants with additional requirements for program scope, processing speed, and communication.
  • CPU 416-2, CPU 416-3, CPU 416-3 PN/DP:
    For plants with high requirements in the top-end performance range.
  • CPU 417-4 DP:
    For plants with the most stringent requirements in the top-end performance range.
  • CPU 412-5H, CPU 414-5H, CPU 416‑5H and CPU 417-4H:
    For SIMATIC S7-400H and S7-400F/FH.
  • CPU 414F-3 PN/DP, CPU 416F-2 and CPU 416F-3 PN/DP:
    For constructing a fail-safe automation system for plants with increased safety requirements.

Обзор

  • 10 different CPUs for S7-400
  • 4 CPUs for S7-400H and S7-400F/FH
  • 3 fail-safe CPUs for S7-400F
  • Graded performance for a wide range of different applications

Дизайн

All CPUs have a plastic housing in which the control and display elements are integrated identically for all CPUs. Identical elements have identical functions.

On the front, there are:

  • LEDs:
    For status and error indication.
  • Toggle switches:
    For selecting the operating modes.
  • Slot for a memory card (expansion of the load memory).
  • Combined MPI/DP interface.
  • Integrated PROFIBUS DP interface (not CPU 412-1).
  • Battery infeed socket:
    For external supply of the battery backup voltage.

All CPUs apart from the entry level CPU 412-1 and CPU 412-2 PN have:

  • PROFIBUS DP interface:
    For interfacing to distributed I/O. Depending on the configuration, it can even be used for communication with an OP or programming device/PC.

In addition, the CPU 412-2 PN, CPU 414-3 PN/DP, CPU 414F-3 PN/DP, CPU 416-3 PN/DP and the CPU 416F-3 PN/DP offer PROFINET connection options. Each of these modules has a PROFINET interface with 2 ports (switch).

The top-end CPUs also have:

  • Spare slots for PROFIBUS DP interface modules:
    For connecting further DP lines.

Otherwise the CPUs only differ with regard to their quantity structure, e.g. RAM, address range, number of loadable blocks, and execution time.

Функции

Memory concept

All CPUs of S7-400 feature two types of memory. This subdivision of work memory increases performance by 100%. Where a standard processor accesses its RAM at least twice, the S7-400 special processor accesses the code memory and data memory simultaneously in one cycle. There are also separate code and data buses for this purpose. The size of the work memory is determined by the appropriate CPU selected from the finely graded CPU spectrum.

For small and medium programs, the integral load memory (RAM) is sufficient. For larger programs, the load memory can be increased by inserting memory cards. Plug-in flash memory cards are available for retentive storage without the need for a battery.

Block encryption

The functions (FCs) and function blocks (FBs) can be stored in the CPU in encrypted form to protect the know-how of the application.

Технические данные

Order number

6ES7412-1XJ05-0AB0

6ES7412-2XJ05-0AB0

6ES7412-2EK07-0AB0

CPU412-1, MPI/DP, 288 KB

CPU412-2, MPI/DP, 512 KB

General information

 

 

 

Product type designation

CPU 412-1

CPU 412-2

CPU 412-2 PN

Engineering with

 

 

 

  • Programming package

STEP7 V 5.3 SP2 or higher with HW update

STEP7 V 5.3 SP2 or higher with HW update

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

Power loss, typ.

2.5 W

4.5 W

5.5 W

Memory

 

 

 

Work memory

 

 

 

  • integrated

288 kbyte

512 kbyte

1 Mbyte

  • integrated (for program)

144 kbyte

256 kbyte

512 kbyte

  • integrated (for data)

144 kbyte

256 kbyte

512 kbyte

Load memory

 

 

 

  • expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • integrated RAM, max.

512 kbyte

512 kbyte

512 kbyte

  • expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

for bit operations, typ.

75 ns

75 ns

31.25 ns

for word operations, typ.

75 ns

75 ns

31.25 ns

for fixed point arithmetic, typ.

75 ns

75 ns

31.25 ns

for floating point arithmetic, typ.

225 ns

225 ns

62.5 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • Number

2 048

2 048

2 048

IEC counter

 

 

 

  • present

Yes

Yes

Yes

S7 times

 

 

 

  • Number

2 048

2 048

2 048

IEC timer

 

 

 

  • present

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

Flag

 

 

 

  • Number, max.

4 kbyte; Size of bit memory address area

4 kbyte; Size of bit memory address area

4 kbyte; Size of bit memory address area

Address area

 

 

 

I/O address area

 

 

 

  • Inputs

4 kbyte

4 kbyte

4 kbyte

  • Outputs

4 kbyte

4 kbyte

4 kbyte

Process image

 

 

 

  • Inputs, adjustable

4 kbyte

4 kbyte

4 kbyte

  • Outputs, adjustable

4 kbyte

4 kbyte

4 kbyte

Hardware configuration

 

 

 

Slots

 

 

 

  • required slots

1

1

1

Time of day

 

 

 

Clock

 

 

 

  • Hardware clock (real-time clock)

Yes

Yes

Yes

Operating hours counter

 

 

 

  • Number

16

16

16

Interfaces

 

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports)

Number of RS 485 interfaces

1; Combined MPI / PROFIBUS DP

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

1; Combined MPI / PROFIBUS DP

1. Interface

 

 

 

Interface type

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

  • MPI

Yes

Yes

Yes

  • DP master

Yes

Yes

Yes

  • DP slave

Yes

Yes

Yes

DP master

 

 

 

  • Number of DP slaves, max.

32

32

32

2. Interface

 

 

 

Interface type

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

Ethernet RJ45

Number of ports

2

Functionality

 

 

 

  • DP master

Yes

No

  • DP slave

Yes

No

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • PROFINET CBA

Yes

DP master

 

 

 

  • Number of DP slaves, max.

64

PROFINET IO Controller

 

 

 

  • Number of connectable IO Devices for RT, max.

256

  • Number of IO Devices with IRT and the option "high flexibility"

256

  • Number of IO Devices with IRT and the option "high performance", max.

64

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Global data communication

 

 

 

  • supported

Yes

Yes

Yes

S7 basic communication

 

 

 

  • supported

Yes

Yes

Yes

S7 communication

 

 

 

  • supported

Yes

Yes

Yes

S5 compatible communication

 

 

 

  • supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

 

  • supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

  • ISO-on-TCP (RFC1006)

Via CP 443-1 Adv. and loadable FB

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs

  • Number of connections, max.

46

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

Web server

 

 

 

  • supported

No

No

Yes

Number of connections

 

 

 

  • overall

32

32

48

Standards, approvals, certificates

 

 

 

Use in hazardous areas

 

 

 

  • ATEX

ATEX II 3 G Ex nA IIC T4 Gc

ATEX II 3 G Ex nA IIC T4 Gc

ATEX II 3 G Ex nA IIC T4 Gc

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • min.

0 °C

0 °C

0 °C

  • max.

60 °C

60 °C

60 °C

Configuration

 

 

 

Programming

 

 

 

Programming language

 

 

 

  • LAD

Yes

Yes

Yes

  • FBD

Yes

Yes

Yes

  • STL

Yes

Yes

Yes

  • SCL

Yes

Yes

Yes

  • CFC

Yes

Yes

Yes

  • GRAPH

Yes

Yes

Yes

  • HiGraph®

Yes

Yes

Yes

Know-how protection

 

 

 

  • User program protection/password protection

Yes

Yes

Yes

  • Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

 

 

 

Width

25 mm

25 mm

25 mm

Height

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

Weights

 

 

 

Weight, approx.

700 g

700 g

750 g


Order number

6ES7414-2XK05-0AB0

6ES7414-3XM05-0AB0

6ES7414-3EM07-0AB0

CPU414-2, MPI/DP, 1 MB

CPU414-3, 2.8 MB, 3 INTERFACES

General information

 

 

 

Product type designation

CPU 414-2

CPU 414-3

CPU414-3 PN/DP

Engineering with

 

 

 

  • Programming package

STEP7 V 5.3 SP2 or higher with HW update

STEP7 V 5.3 SP2 or higher with HW update

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

Power loss, typ.

4.5 W

5.5 W

6.5 W

Memory

 

 

 

Work memory

 

 

 

  • integrated

1 Mbyte

2.8 Mbyte

4 Mbyte

  • integrated (for program)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

  • integrated (for data)

0.5 Mbyte

1.4 Mbyte

2 Mbyte

Load memory

 

 

 

  • expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • integrated RAM, max.

512 kbyte

512 kbyte

512 kbyte

  • expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

for bit operations, typ.

45 ns

45 ns

18.75 ns

for word operations, typ.

45 ns

45 ns

18.75 ns

for fixed point arithmetic, typ.

45 ns

45 ns

18.75 ns

for floating point arithmetic, typ.

135 ns

135 ns

37.5 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • Number

2 048

2 048

2 048

IEC counter

 

 

 

  • present

Yes

Yes

Yes

S7 times

 

 

 

  • Number

2 048

2 048

2 048

IEC timer

 

 

 

  • present

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

Flag

 

 

 

  • Number, max.

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

8 kbyte; Size of bit memory address area

Address area

 

 

 

I/O address area

 

 

 

  • Inputs

8 kbyte

8 kbyte

8 kbyte

  • Outputs

8 kbyte

8 kbyte

8 kbyte

Process image

 

 

 

  • Inputs, adjustable

8 kbyte

8 kbyte

8 kbyte

  • Outputs, adjustable

8 kbyte

8 kbyte

8 kbyte

Hardware configuration

 

 

 

Slots

 

 

 

  • required slots

1

2

2

Time of day

 

 

 

Clock

 

 

 

  • Hardware clock (real-time clock)

Yes

Yes

Yes

Operating hours counter

 

 

 

  • Number

16

16

16

Interfaces

 

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable)

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

1; Combined MPI / PROFIBUS DP

Number of other interfaces

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

 

 

Interface type

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

  • MPI

Yes

Yes

Yes

  • DP master

Yes

Yes

Yes

  • DP slave

Yes

Yes

Yes

DP master

 

 

 

  • Number of DP slaves, max.

32

32

32

2. Interface

 

 

 

Interface type

Integrated

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Ethernet RJ45

Number of ports

2

Functionality

 

 

 

  • DP master

Yes

Yes

No

  • DP slave

Yes

Yes

No

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • PROFINET CBA

Yes

DP master

 

 

 

  • Number of DP slaves, max.

96

96

PROFINET IO Controller

 

 

 

  • Number of connectable IO Devices for RT, max.

256

  • Number of IO Devices with IRT and the option "high flexibility"

256

  • Number of IO Devices with IRT and the option "high performance", max.

64

3. Interface

 

 

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Functionality

 

 

 

  • MPI

No

No

  • DP master

Yes

Yes

  • DP slave

Yes

Yes

DP master

 

 

 

  • Number of DP slaves, max.

96

96

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Global data communication

 

 

 

  • supported

Yes

Yes

Yes

S7 basic communication

 

 

 

  • supported

Yes

Yes

Yes

S7 communication

 

 

 

  • supported

Yes

Yes

Yes

S5 compatible communication

 

 

 

  • supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

 

  • supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

  • ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs

  • Number of connections, max.

62

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

Web server

 

 

 

  • supported

No

No

Yes

Number of connections

 

 

 

  • overall

32

32

64

Standards, approvals, certificates

 

 

 

Use in hazardous areas

 

 

 

  • ATEX

ATEX II 3 G Ex nA IIC T4 Gc

ATEX II 3 G Ex nA IIC T4 Gc

ATEX II 3 G Ex nA IIC T4 Gc

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • min.

0 °C

0 °C

0 °C

  • max.

60 °C

60 °C

60 °C

Configuration

 

 

 

Programming

 

 

 

Programming language

 

 

 

  • LAD

Yes

Yes

Yes

  • FBD

Yes

Yes

Yes

  • STL

Yes

Yes

Yes

  • SCL

Yes

Yes

Yes

  • CFC

Yes

Yes

Yes

  • GRAPH

Yes

Yes

Yes

  • HiGraph®

Yes

Yes

Yes

Know-how protection

 

 

 

  • User program protection/password protection

Yes

Yes

Yes

  • Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

 

 

 

Width

25 mm

50 mm

50 mm

Height

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

Weights

 

 

 

Weight, approx.

700 g

900 g

900 g


Order number

6ES7416-2XN05-0AB0

6ES7416-3XR05-0AB0

6ES7416-3ES07-0AB0

CPU 416-2, MPI, PROFIBUS, 5.6 MB

CPU 416-3, 11.2 MB, 3 INTERFACES

General information

 

 

 

Product type designation

CPU 416-2

CPU 416-3

CPU416-3 PN/DP

Engineering with

 

 

 

  • Programming package

STEP7 V 5.3 SP2 or higher with HW update

STEP7 V 5.3 SP2 or higher with HW update

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

Power loss, typ.

4.5 W

5.5 W

6.5 W

Memory

 

 

 

Work memory

 

 

 

  • integrated

5.6 Mbyte

11.2 Mbyte

16 Mbyte

  • integrated (for program)

2.8 Mbyte

5.6 Mbyte

8 Mbyte

  • integrated (for data)

2.8 Mbyte

5.6 Mbyte

8 Mbyte

Load memory

 

 

 

  • expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

  • integrated RAM, max.

1 Mbyte

1 Mbyte

1 Mbyte

  • expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

for bit operations, typ.

30 ns

30 ns

12.5 ns

for word operations, typ.

30 ns

30 ns

12.5 ns

for fixed point arithmetic, typ.

30 ns

30 ns

12.5 ns

for floating point arithmetic, typ.

90 ns

90 ns

25 ns

Counters, timers and their retentivity

 

 

 

S7 counter

 

 

 

  • Number

2 048

2 048

2 048

IEC counter

 

 

 

  • present

Yes

Yes

Yes

S7 times

 

 

 

  • Number

2 048

2 048

2 048

IEC timer

 

 

 

  • present

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

Flag

 

 

 

  • Number, max.

16 kbyte; Size of bit memory address area

16 kbyte; Size of bit memory address area

16 kbyte; Size of bit memory address area

Address area

 

 

 

I/O address area

 

 

 

  • Inputs

16 kbyte

16 kbyte

16 kbyte

  • Outputs

16 kbyte

16 kbyte

16 kbyte

Process image

 

 

 

  • Inputs, adjustable

16 kbyte

16 kbyte

16 kbyte

  • Outputs, adjustable

16 kbyte

16 kbyte

16 kbyte

Hardware configuration

 

 

 

Slots

 

 

 

  • required slots

1

2

2

Time of day

 

 

 

Clock

 

 

 

  • Hardware clock (real-time clock)

Yes

Yes

Yes

Operating hours counter

 

 

 

  • Number

16

16

16

Interfaces

 

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable)

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

2

1; Combined MPI / PROFIBUS DP

Number of other interfaces

0

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

 

 

Interface type

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

  • MPI

Yes

Yes

Yes

  • DP master

Yes

Yes

Yes

  • DP slave

Yes

Yes

Yes

DP master

 

 

 

  • Number of DP slaves, max.

32

32

32

2. Interface

 

 

 

Interface type

Integrated

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Ethernet RJ45

Number of ports

2

Functionality

 

 

 

  • DP master

Yes

Yes

No

  • DP slave

Yes

Yes

No

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • PROFINET CBA

Yes

DP master

 

 

 

  • Number of DP slaves, max.

125

125

PROFINET IO Controller

 

 

 

  • Number of connectable IO Devices for RT, max.

256

  • Number of IO Devices with IRT and the option "high flexibility"

256

  • Number of IO Devices with IRT and the option "high performance", max.

64

3. Interface

 

 

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Functionality

 

 

 

  • MPI

No

No

  • DP master

Yes

Yes

  • DP slave

Yes

Yes

DP master

 

 

 

  • Number of DP slaves, max.

125

125

Isochronous mode

 

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

 

PG/OP communication

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Global data communication

 

 

 

  • supported

Yes

Yes

Yes

S7 basic communication

 

 

 

  • supported

Yes

Yes

Yes

S7 communication

 

 

 

  • supported

Yes

Yes

Yes

S5 compatible communication

 

 

 

  • supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

 

  • supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

  • ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

  • Number of connections, max.

94

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

Web server

 

 

 

  • supported

No

No

Yes

Number of connections

 

 

 

  • overall

64

64

96

Standards, approvals, certificates

 

 

 

Use in hazardous areas

 

 

 

  • ATEX

ATEX II 3 G Ex nA IIC T4 Gc

ATEX II 3 G Ex nA IIC T4 Gc

ATEX II 3 G Ex nA IIC T4 Gc

Ambient conditions

 

 

 

Ambient temperature during operation

 

 

 

  • min.

0 °C

0 °C

0 °C

  • max.

60 °C

60 °C

60 °C

Configuration

 

 

 

Programming

 

 

 

Programming language

 

 

 

  • LAD

Yes

Yes

Yes

  • FBD

Yes

Yes

Yes

  • STL

Yes

Yes

Yes

  • SCL

Yes

Yes

Yes

  • CFC

Yes

Yes

Yes

  • GRAPH

Yes

Yes

Yes

  • HiGraph®

Yes

Yes

Yes

Know-how protection

 

 

 

  • User program protection/password protection

Yes

Yes

Yes

  • Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

 

 

 

Width

25 mm

50 mm

50 mm

Height

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

Weights

 

 

 

Weight, approx.

720 g

900 g

900 g


Order number

6ES7417-4XT07-0AB0

General information

 

Product type designation

CPU 417-4

Engineering with

 

  • Programming package

STEP 7 V5.4 or higher with HSP 261

Supply voltage

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

Power loss

 

Power loss, typ.

6.5 W

Memory

 

Work memory

 

  • integrated

32 Mbyte

  • integrated (for program)

16 Mbyte

  • integrated (for data)

16 Mbyte

Load memory

 

  • expandable FEPROM, max.

64 Mbyte

  • integrated RAM, max.

1 Mbyte

  • expandable RAM, max.

64 Mbyte

CPU processing times

 

for bit operations, typ.

7.5 ns

for word operations, typ.

7.5 ns

for fixed point arithmetic, typ.

7.5 ns

for floating point arithmetic, typ.

15 ns

Counters, timers and their retentivity

 

S7 counter

 

  • Number

2 048

IEC counter

 

  • present

Yes

S7 times

 

  • Number

2 048

IEC timer

 

  • present

Yes

Data areas and their retentivity

 

Flag

 

  • Number, max.

16 kbyte; Size of bit memory address area

Address area

 

I/O address area

 

  • Inputs

16 kbyte

  • Outputs

16 kbyte

Process image

 

  • Inputs, adjustable

16 kbyte

  • Outputs, adjustable

16 kbyte

Hardware configuration

 

Slots

 

  • required slots

2

Time of day

 

Clock

 

  • Hardware clock (real-time clock)

Yes

Operating hours counter

 

  • Number

16

Interfaces

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 2 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

Number of other interfaces

2; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS + MPI

Functionality

 

  • MPI

Yes

  • DP master

Yes

  • DP slave

Yes

DP master

 

  • Number of DP slaves, max.

32

2. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS

Functionality

 

  • DP master

Yes

  • DP slave

Yes

DP master

 

  • Number of DP slaves, max.

125

3. Interface

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

Functionality

 

  • MPI

No

  • DP master

Yes

  • DP slave

Yes

DP master

 

  • Number of DP slaves, max.

125

4. Interface

 

Interface type

Pluggable interface module (IF), technical data as for 2nd interface

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Communication functions

 

PG/OP communication

Yes

Data record routing

Yes

Global data communication

 

  • supported

Yes

S7 basic communication

 

  • supported

Yes

S7 communication

 

  • supported

Yes

S5 compatible communication

 

  • supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

  • supported

Yes; Via CP and loadable FB

Open IE communication

 

  • ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Web server

 

  • supported

No

Number of connections

 

  • overall

120

Standards, approvals, certificates

 

Use in hazardous areas

 

  • ATEX

ATEX II 3 G Ex nA IIC T4 Gc

Ambient conditions

 

Ambient temperature during operation

 

  • min.

0 °C

  • max.

60 °C

Configuration

 

Programming

 

Programming language

 

  • LAD

Yes

  • FBD

Yes

  • STL

Yes

  • SCL

Yes

  • CFC

Yes

  • GRAPH

Yes

  • HiGraph®

Yes

Know-how protection

 

  • User program protection/password protection

Yes

  • Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

50 mm

Height

290 mm

Depth

219 mm

Weights

 

Weight, approx.

900 g


Order number

6ES7414-3FM07-0AB0

General information

 

Product type designation

CPU414F-3 PN/DP

Engineering with

 

  • Programming package

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

Power loss

 

Power loss, typ.

6.5 W

Memory

 

Work memory

 

  • integrated

4 Mbyte

  • integrated (for program)

2 Mbyte

  • integrated (for data)

2 Mbyte

Load memory

 

  • expandable FEPROM, max.

64 Mbyte

  • integrated RAM, max.

512 kbyte

  • expandable RAM, max.

64 Mbyte

CPU processing times

 

for bit operations, typ.

18.75 ns

for word operations, typ.

18.75 ns

for fixed point arithmetic, typ.

18.75 ns

for floating point arithmetic, typ.

37.5 ns

Counters, timers and their retentivity

 

S7 counter

 

  • Number

2 048

IEC counter

 

  • present

Yes

S7 times

 

  • Number

2 048

IEC timer

 

  • present

Yes

Data areas and their retentivity

 

Flag

 

  • Number, max.

8 kbyte; Size of bit memory address area

Address area

 

I/O address area

 

  • Inputs

8 kbyte

  • Outputs

8 kbyte

Process image

 

  • Inputs, adjustable

8 kbyte

  • Outputs, adjustable

8 kbyte

Hardware configuration

 

Slots

 

  • required slots

2

Time of day

 

Clock

 

  • Hardware clock (real-time clock)

Yes

Operating hours counter

 

  • Number

16

Interfaces

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

1; Combined MPI / PROFIBUS DP

Number of other interfaces

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

Interface type

Integrated

Physics

RS 485 / PROFIBUS + MPI

Functionality

 

  • MPI

Yes

  • DP master

Yes

  • DP slave

Yes

DP master

 

  • Number of DP slaves, max.

32

2. Interface

 

Interface type

PROFINET

Physics

Ethernet RJ45

Number of ports

2

Functionality

 

  • DP master

No

  • DP slave

No

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • PROFINET CBA

Yes

PROFINET IO Controller

 

  • Number of connectable IO Devices for RT, max.

256

  • Number of IO Devices with IRT and the option "high flexibility"

256

  • Number of IO Devices with IRT and the option "high performance", max.

64

3. Interface

 

Interface type

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

Functionality

 

  • MPI

No

  • DP master

Yes

  • DP slave

Yes

DP master

 

  • Number of DP slaves, max.

96

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

PG/OP communication

Yes

Data record routing

Yes

Global data communication

 

  • supported

Yes

S7 basic communication

 

  • supported

Yes

S7 communication

 

  • supported

Yes

S5 compatible communication

 

  • supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

  • supported

Yes; Via CP and loadable FB

Open IE communication

 

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

  • ISO-on-TCP (RFC1006)

Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs

  • Number of connections, max.

62

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

62

Web server

 

  • supported

Yes

Number of connections

 

  • overall

64

Standards, approvals, certificates

 

Use in hazardous areas

 

  • ATEX

ATEX II 3 G Ex nA IIC T4 Gc

Ambient conditions

 

Ambient temperature during operation

 

  • min.

0 °C

  • max.

60 °C

Configuration

 

Programming

 

Programming language

 

  • LAD

Yes

  • FBD

Yes

  • STL

Yes

  • SCL

Yes

  • CFC

Yes

  • GRAPH

Yes

  • HiGraph®

Yes

Know-how protection

 

  • User program protection/password protection

Yes

  • Block encryption

Yes; With S7 block Privacy

Dimensions

 

Width

50 mm

Height

290 mm

Depth

219 mm

Weights

 

Weight, approx.

900 g


Order number

6ES7416-2FN05-0AB0

6ES7416-3FS07-0AB0

CPU 416F-2, MPI, PROFIBUS, 5.6 MB

General information

 

 

Product type designation

CPU 416F-2

CPU416F-3 PN/DP

Engineering with

 

 

  • Programming package

STEP 7 V5.3 SP2 or higher with hardware update, Distributed Safety V5.2 SP2 or higher

STEP 7 V5.5 or higher with HSP 262

Supply voltage

 

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

Power loss, typ.

4.5 W

6.5 W

Memory

 

 

Work memory

 

 

  • integrated

5.6 Mbyte

16 Mbyte

  • integrated (for program)

2.8 Mbyte

8 Mbyte

  • integrated (for data)

2.8 Mbyte

8 Mbyte

Load memory

 

 

  • expandable FEPROM, max.

64 Mbyte

64 Mbyte

  • integrated RAM, max.

1 Mbyte

1 Mbyte

  • expandable RAM, max.

64 Mbyte

64 Mbyte

CPU processing times

 

 

for bit operations, typ.

30 ns

12.5 ns

for word operations, typ.

30 ns

12.5 ns

for fixed point arithmetic, typ.

30 ns

12.5 ns

for floating point arithmetic, typ.

90 ns

25 ns

Counters, timers and their retentivity

 

 

S7 counter

 

 

  • Number

2 048

2 048

IEC counter

 

 

  • present

Yes

Yes

S7 times

 

 

  • Number

2 048

2 048

IEC timer

 

 

  • present

Yes

Yes

Data areas and their retentivity

 

 

Flag

 

 

  • Number, max.

16 kbyte; Size of bit memory address area

16 kbyte; Size of bit memory address area

Address area

 

 

I/O address area

 

 

  • Inputs

16 kbyte

16 kbyte

  • Outputs

16 kbyte

16 kbyte

Process image

 

 

  • Inputs, adjustable

16 kbyte

16 kbyte

  • Outputs, adjustable

16 kbyte

16 kbyte

Hardware configuration

 

 

Slots

 

 

  • required slots

1

2

Time of day

 

 

Clock

 

 

  • Hardware clock (real-time clock)

Yes

Yes

Operating hours counter

 

 

  • Number

16

16

Interfaces

 

 

Interfaces/bus type

1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable)

Number of RS 485 interfaces

2; Combined MPI / PROFIBUS DP and PROFIBUS DP

1; Combined MPI / PROFIBUS DP

Number of other interfaces

1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0)

1. Interface

 

 

Interface type

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

  • MPI

Yes

Yes

  • DP master

Yes

Yes

  • DP slave

Yes

Yes

DP master

 

 

  • Number of DP slaves, max.

32

32

2. Interface

 

 

Interface type

Integrated

PROFINET

Physics

RS 485 / PROFIBUS

Ethernet RJ45

Number of ports

2

Functionality

 

 

  • DP master

Yes

No

  • DP slave

Yes

No

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

Yes

  • PROFINET CBA

Yes

DP master

 

 

  • Number of DP slaves, max.

125

PROFINET IO Controller

 

 

  • Number of connectable IO Devices for RT, max.

256

  • Number of IO Devices with IRT and the option "high flexibility"

256

  • Number of IO Devices with IRT and the option "high performance", max.

64

3. Interface

 

 

Interface type

Pluggable interface module (IF)

Plug-in interface modules

IF 964-DP (MLFB: 6ES7964-2AA04-0AB0)

Physics

RS 485 / PROFIBUS

Functionality

 

 

  • MPI

No

  • DP master

Yes

  • DP slave

Yes

DP master

 

 

  • Number of DP slaves, max.

125

Isochronous mode

 

 

Isochronous operation (application synchronized up to terminal)

Yes; For PROFIBUS only

Yes; Via PROFIBUS DP or PROFINET interface

Communication functions

 

 

PG/OP communication

Yes

Yes

Data record routing

Yes

Yes

Global data communication

 

 

  • supported

Yes

Yes

S7 basic communication

 

 

  • supported

Yes

Yes

S7 communication

 

 

  • supported

Yes

Yes

S5 compatible communication

 

 

  • supported

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5

Standard communication (FMS)

 

 

  • supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

  • ISO-on-TCP (RFC1006)

Via CP 443-1 and loadable FB

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

  • Number of connections, max.

94

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

94

Web server

 

 

  • supported

No

Yes

Number of connections

 

 

  • overall

64

96

Standards, approvals, certificates

 

 

Use in hazardous areas

 

 

  • ATEX

ATEX II 3 G Ex nA IIC T4 Gc

ATEX II 3 G Ex nA IIC T4 Gc

Ambient conditions

 

 

Ambient temperature during operation

 

 

  • min.

0 °C

0 °C

  • max.

60 °C

60 °C

Configuration

 

 

Programming

 

 

Programming language

 

 

  • LAD

Yes

Yes

  • FBD

Yes

Yes

  • STL

Yes

Yes

  • SCL

Yes

Yes

  • CFC

Yes

Yes

  • GRAPH

Yes

Yes

  • HiGraph®

Yes

Yes

Know-how protection

 

 

  • User program protection/password protection

Yes

Yes

  • Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

 

 

Width

25 mm

50 mm

Height

290 mm

290 mm

Depth

219 mm

219 mm

Weights

 

 

Weight, approx.

700 g

900 g


Order number

6ES7412-5HK06-0AB0

6ES7414-5HM06-0AB0

6ES7416-5HS06-0AB0

6ES7417-5HT06-0AB0

CPU412-5H PN/DP, 1MB F. S7-400H/F/FH

CPU414-5H PN/DP, 4MB F. S7-400H/F/FH

CPU416-5H PN/DP, 16MB F. S7-400H/F/FH

CPU417-5H PN/DP, 32MB F. S7-400H/F/FH

General information

 

 

 

 

Product type designation

CPU 412-5H PN/DP

CPU 414-5H PN/DP

CPU 416-5H PN/DP

CPU 417-5H PN/DP

Engineering with

 

 

 

 

  • Programming package

As of STEP 7 V5.5 SP2 with HF1

As of STEP 7 V5.5 SP2 with HF1

As of STEP 7 V5.5 SP2 with HF1

As of STEP 7 V5.5 SP2 with HF1

Supply voltage

 

 

 

 

Rated value (DC)

  • 24 V DC

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

No; Power supply via system power supply

Power loss

 

 

 

 

Power loss, typ.

7.5 W

7.5 W

7.5 W

7.5 W

Memory

 

 

 

 

Work memory

 

 

 

 

  • integrated

1 Mbyte

4 Mbyte

16 Mbyte

32 Mbyte

  • integrated (for program)

512 kbyte

2 Mbyte

6 Mbyte

16 Mbyte

  • integrated (for data)

512 kbyte

2 Mbyte

10 Mbyte

16 Mbyte

Load memory

 

 

 

 

  • expandable FEPROM, max.

64 Mbyte

64 Mbyte

64 Mbyte

64 Mbyte

  • integrated RAM, max.

512 kbyte

512 kbyte

1 Mbyte

1 Mbyte

  • expandable RAM, max.

64 Mbyte

64 Mbyte

64 Mbyte

64 Mbyte

CPU processing times

 

 

 

 

for bit operations, typ.

31.25 ns

18.75 ns

12.5 ns

7.5 ns

for word operations, typ.

31.25 ns

18.75 ns

12.5 ns

7.5 ns

for fixed point arithmetic, typ.

31.25 ns

18.75 ns

12.5 ns

7.5 ns

for floating point arithmetic, typ.

62.5 ns

37.5 ns

25 ns

15 ns

Counters, timers and their retentivity

 

 

 

 

S7 counter

 

 

 

 

  • Number

2 048

2 048

2 048

2 048

IEC counter

 

 

 

 

  • present

Yes

Yes

Yes

Yes

S7 times

 

 

 

 

  • Number

2 048

2 048

2 048

2 048

IEC timer

 

 

 

 

  • present

Yes

Yes

Yes

Yes

Data areas and their retentivity

 

 

 

 

Flag

 

 

 

 

  • Number, max.

8 192 byte

8 192 byte

16 384 byte

16 384 byte

Address area

 

 

 

 

I/O address area

 

 

 

 

  • Inputs

8 kbyte

8 kbyte

16 kbyte

16 kbyte

  • Outputs

8 kbyte

8 kbyte

16 kbyte

16 kbyte

Process image

 

 

 

 

  • Inputs, adjustable

8 kbyte

8 kbyte

16 kbyte

16 kbyte

  • Outputs, adjustable

8 kbyte

8 kbyte

16 kbyte

16 kbyte

Hardware configuration

 

 

 

 

Slots

 

 

 

 

  • required slots

2

2

2

2

Time of day

 

 

 

 

Clock

 

 

 

 

  • Hardware clock (real-time clock)

Yes

Yes

Yes

Yes

Operating hours counter

 

 

 

 

  • Number

16

16

16

16

Interfaces

 

 

 

 

Number of RS 485 interfaces

2

2

2

2

Number of other interfaces

2; Fiber-optic interface

2; Fiber-optic interface

2; Fiber-optic interface

2; Fiber-optic interface

1. Interface

 

 

 

 

Interface type

Integrated

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

RS 485 / PROFIBUS + MPI

Functionality

 

 

 

 

  • MPI

Yes

Yes

Yes

Yes

  • DP master

Yes

Yes

Yes

Yes

  • DP slave

No

No

No

No

DP master

 

 

 

 

  • Number of DP slaves, max.

32

32

32

32

2. Interface

 

 

 

 

Interface type

PROFINET

PROFINET

PROFINET

PROFINET

Physics

Ethernet RJ45

Ethernet RJ45

Ethernet RJ45

Ethernet RJ45

Number of ports

2

2

2

2

Functionality

 

 

 

 

  • DP master

No

No

No

No

  • DP slave

No

No

No

No

  • PROFINET IO Controller

Yes

Yes

Yes

Yes

  • PROFINET IO Device

No

No

No

No

  • PROFINET CBA

No

No

No

No

PROFINET IO Controller

 

 

 

 

  • Number of connectable IO Devices for RT, max.

256

256

256

256

3. Interface

 

 

 

 

Interface type

Integrated

Integrated

Integrated

Integrated

Physics

RS 485 / PROFIBUS

RS 485 / PROFIBUS

RS 485 / PROFIBUS

RS 485 / PROFIBUS

Functionality

 

 

 

 

  • DP master

Yes

Yes

Yes

Yes

  • DP slave

No

No

No

No

DP master

 

 

 

 

  • Number of DP slaves, max.

64

96

125

125

4. Interface

 

 

 

 

Interface type

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

5. Interface

 

 

 

 

Interface type

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Pluggable synchronization submodule (FO)

Plug-in interface modules

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Synchronization modules 6ES7960-1AA06-0XA0 or 6ES7960-1AB06-0XA0

Isochronous mode

 

 

 

 

Isochronous operation (application synchronized up to terminal)

No

No

No

No

Communication functions

 

 

 

 

PG/OP communication

Yes

Yes

Yes

Yes

Data record routing

Yes

Yes

Yes

Yes

S7 routing

Yes

Yes

Yes

Yes

Global data communication

 

 

 

 

  • supported

No

No

No

No

S7 basic communication

 

 

 

 

  • supported

No

No

No

No

S7 communication

 

 

 

 

  • supported

Yes

Yes

Yes

Yes

S5 compatible communication

 

 

 

 

  • supported

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Yes; (via CP max. 10 and FC AG_SEND and FC AG_RECV)

Standard communication (FMS)

 

 

 

 

  • supported

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Yes; Via CP and loadable FB

Open IE communication

 

 

 

 

  • TCP/IP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

62

94

118

  • ISO-on-TCP (RFC1006)

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs

  • Number of connections, max.

46

62

94

118

  • UDP

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

Yes; via integrated PROFINET interface and loadable FBs

  • Number of connections, max.

46

62

94

118

Web server

 

 

 

 

  • supported

No

No

No

No

Number of connections

 

 

 

 

  • overall

48

64

96

120

Configuration

 

 

 

 

Programming

 

 

 

 

Programming language

 

 

 

 

  • LAD

Yes

Yes

Yes

Yes

  • FBD

Yes

Yes

Yes

Yes

  • STL

Yes

Yes

Yes

Yes

  • SCL

Yes

Yes

Yes

Yes

  • CFC

Yes

Yes

Yes

Yes

  • GRAPH

Yes

Yes

Yes

Yes

  • HiGraph®

Yes

Yes

Yes

Yes

Know-how protection

 

 

 

 

  • User program protection/password protection

Yes

Yes

Yes

Yes

  • Block encryption

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Yes; With S7 block Privacy

Dimensions

 

 

 

 

Width

50 mm

50 mm

50 mm

50 mm

Height

290 mm

290 mm

290 mm

290 mm

Depth

219 mm

219 mm

219 mm

219 mm

Weights

 

 

 

 

Weight, approx.

995 g

995 g

995 g

995 g


Дальнейшая информация

Brochures

Information material for downloading can be found in the Internet:

http://www.automation.siemens.com/infocenter

preloader

40000