The subracks form the basic mechanical framework of the SIMATIC S7-400. Their functions are as follows:
The subracks are designed for wall mounting and installation in frames and cabinets
Various subracks are available for setting up the SIMATIC S7-400.
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme
All racks included:
Order number | 6AG1400-1TA11-7AA0 | 6AG1400-1JA11-7AA0 | 6AG1400-2JA10-7AA0 | |
---|---|---|---|---|
SIPLUS S7-400 RACK UR1 18SLOT ALU | SIPLUS S-400 RACK UR2 9SLOT ALU | SIPLUS S7-400 BGT UR2-H 2X9SLOT ALU | ||
Hardware configuration |
|
|
| |
Rack |
|
|
| |
| Yes | Yes | Yes | |
| Yes | Yes | Yes | |
Slots |
|
|
| |
| 18 | 9 | 18 | |
Ambient conditions |
|
|
| |
Ambient temperature during operation |
|
|
| |
| -25 °C; = Tmin | -25 °C; = Tmin | -25 °C; = Tmin | |
| 70 °C; = Tmax | 70 °C; = Tmax | 70 °C; = Tmax | |
Extended ambient conditions |
|
|
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | |
Relative humidity |
|
|
| |
| 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | |
Resistance |
|
|
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Dimensions |
|
|
| |
Width | 482.5 mm | 257.5 mm | 482.5 mm | |
Height | 290 mm | 290 mm | 290 mm | |
Depth | 27.5 mm | 27.5 mm | 27.5 mm | |
Weights |
|
|
| |
Weight, approx. | 3 kg | 1.5 kg | 3 000 g |