The power supplies supply the S7-400 modules with their 5 V DC and 24 V DC operating voltages via the backplane bus.
Power supplies are available for AC line voltages of 85 to 264 V and for DC voltages of 19.2 to 300 V.
One power supply module is required per rack.
Exception:
With interfaces with current transfer, the power supply module in the central controller also supplies all modules in the expansion units.
The load voltage for supplying sensors and actuators must be made available separately.
There are also power supplies to make both the standard system and the H system fail-safe (redundant power supplies).
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme specific information was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme
The power supply modules are inserted at the far left in the rack (starting from slot 1). Depending on the version, they occupy slots 1 to 3. The modules are enclosed and are cooled via natural convection.
The front of the module contains:
The back-up battery is optional and must be ordered in addition. For power supplies at and above 10 A, two back-up batteries are recommended.
Order number | 6AG1405-0KA02-7AA0 | 6AG1405-0KR02-7AA0 | 6AG1407-0KA02-7AA0 | 6AG1407-0KR02-7AA0 | |
---|---|---|---|---|---|
SIPLUS PS 405 10A | SIPLUS S7-400 PS405 10A | SIPLUS S7-400 PS407 10A | SIPLUS S7-400 PS407 10A | ||
General information |
|
|
|
| |
Product type designation | PS405, 24/48/60 VDC, 5 VDC/10 A | PS405,24/48/60 VDC,5 VDC/10 A,RED | PS407,UC 120/230 V,5 VDC/10 A,RED. | ||
Supply voltage |
|
|
|
| |
Rated value (DC) | |||||
| Yes | Yes | |||
| Yes | Yes | |||
| Yes | Yes | |||
| Yes | Yes | |||
| Yes | Yes | |||
permissible range, lower limit (DC) | 19.2 V; Dynamic 18.5 V | 19.2 V; Dynamic 18.5 V | 88 V | 88 V | |
permissible range, upper limit (DC) | 72 V; dynamic 75.5 V | 72 V; dynamic 75.5 V | 300 V | 300 V | |
Rated value (AC) | |||||
| Yes | Yes | |||
| Yes | Yes | |||
permissible range, lower limit (AC) | 85 V | 85 V | |||
permissible range, upper limit (AC) | 264 V | 264 V | |||
Line frequency |
|
|
|
| |
| Yes | Yes | |||
| Yes | Yes | |||
| 47 Hz | 47 Hz | |||
| 63 Hz | 63 Hz | |||
Mains buffering |
|
|
|
| |
| 20 ms | 20 ms | 20 ms | 20 ms | |
| Yes | Yes | Yes | Yes | |
Input current |
|
|
|
| |
Rated value at 24 V DC | 4 A | 4 A | |||
Rated value at 48 V DC | 2 A | 2 A | |||
Rated value at 60 V DC | 1.6 A | 1.6 A | |||
Rated value at 110 V DC | 1 A; at 120 V DC | 1 A; at 120 V DC | |||
Rated value at 230 V DC | 0.5 A | 0.5 A | |||
Rated value at 120 V AC | 0.9 A | 0.9 A | |||
Rated value at 230 V AC | 0.5 A | 0.5 A | |||
Inrush current, max. | 18 A; Full width at half maximum 20 ms | 18 A; Full width at half maximum 20 ms | 63 A; Full width at half maximum 1 ms | 63 A; Full width at half maximum 1 ms | |
Output voltage |
|
|
|
| |
Type of output voltage | DC | DC | DC | ||
Rated value (DC) | |||||
| Yes | Yes | Yes | Yes | |
| Yes | Yes | Yes | Yes | |
Output current |
|
|
|
| |
for backplane bus (5 V DC), max. | 10 A; 7A @ > 60 °C, no base load necessary | 10 A; no base load required | 10 A; no base load required | 10 A; no base load required | |
for backplane bus (24 V DC), max. | 1 A; idling-proof | 1 A; idling-proof | 1 A; idling-proof | 1 A; idling-proof | |
short-circuit protection | Yes | Yes | Yes | Yes | |
Power |
|
|
|
| |
Power consumption, typ. | 95 W | 95 W | 95 W | 95 W | |
Power loss |
|
|
|
| |
Power loss, typ. | 20 W | 20 W | 20 W | 20 W | |
Battery |
|
|
|
| |
Backup battery |
|
|
|
| |
| Yes; 2x lithium AA; 3.6 V / 2.3 Ah | Yes; 0 °C to +60 °C: 2 x lithium AA; 3.6 V/2.3 Ah // -25 °C to +70 °C and/or 100% RH: 2 x external battery box 6AG1971-0AA00-7AA0 and 2 x MONO cell design D | Yes; 0 °C to +60 °C: 2 x lithium AA; 3.6 V/2.3 Ah // -25 °C to +70 °C and/or 100% RH: 2 x external battery box 6AG1971-0AA00-7AA0 and 2 x MONO cell design D | Yes; 0 °C to +60 °C: 2 x lithium AA; 3.6 V/2.3 Ah // -25 °C to +70 °C and/or 100% RH: 2 x external battery box 6AG1971-0AA00-7AA0 and 2 x MONO cell design D | |
Hardware configuration |
|
|
|
| |
Slots |
|
|
|
| |
| 2 | 2 | 2 | 2 | |
Potential separation |
|
|
|
| |
primary/secondary | Yes | Yes | Yes | Yes | |
EMC |
|
|
|
| |
Compliance with line harmonic distortion limits |
|
|
|
| |
| Yes | Yes | |||
Degree and class of protection |
|
|
|
| |
Protection class | 1; with protective conductor | 1; with protective conductor | 1; with protective conductor | 1; with protective conductor | |
Ambient conditions |
|
|
|
| |
Ambient temperature during operation |
|
|
|
| |
| -25 °C; = Tmin | -25 °C; = Tmin; using the external battery box SIPLUS 6AG1971-0AA00-7AA0 for buffer mode | -25 °C; using the external battery box SIPLUS 6AG1971-0AA00-7AA0 for buffer mode | -25 °C; using the external battery box SIPLUS 6AG1971-0AA00-7AA0 for buffer mode | |
| 70 °C; = Tmax | 70 °C; = Tmax; using the external battery box SIPLUS 6AG1971-0AA00-7AA0 for buffer mode | 70 °C; using the external battery box SIPLUS 6AG1971-0AA00-7AA0 for buffer mode | 70 °C; using the external battery box SIPLUS 6AG1971-0AA00-7AA0 for buffer mode | |
Extended ambient conditions |
|
|
|
| |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | |
Relative humidity |
|
|
|
| |
| 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning if there is condensation). In buffer mode, use battery box SIPLUS 6AG1971-0AA00-7AA0 for high humidity | 100 %; RH incl. condensation/frost (no commissioning if there is condensation). In buffer mode, use battery box SIPLUS 6AG1971-0AA00-7AA0 for high humidity | 100 %; RH incl. condensation/frost (no commissioning if there is condensation). In buffer mode, use battery box SIPLUS 6AG1971-0AA00-7AA0 for high humidity | |
Resistance |
|
|
|
| |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
Connection method |
|
|
|
| |
Connecting cables/cross-sections | 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm | 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm | 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm | 3x 1.5 mm², solid or stranded wire with end sleeve, external diameter 3 mm to 9 mm | |
Dimensions |
|
|
|
| |
Width | 50 mm | 50 mm | 50 mm | 50 mm | |
Height | 290 mm | 290 mm | 290 mm | 290 mm | |
Depth | 217 mm | 217 mm | 217 mm | 217 mm | |
Weights |
|
|
|
| |
Weight, approx. | 1.2 kg | 1 200 g | 1 200 g | 1 200 g |