preloader
mail@uselogic.ru  +7(495) 374 68 44 Заказать звонок

Обзор

Class CC fuses are used for “branch circuit protection".

The enclosed fuse holders are designed and tested to comply with the US National Electrical Code NEC 210.20(A). This means that when subject to continuous operation, only 80 % of the rated current is permissible as operational current.

An operational current of 100 % of the rated current (30 A) is only permissible short-time.

The devices are prepared for the inscription labels of the ALPHA FIX terminal blocks 8WH8 120-7AA15 and 8WH8 120-7XA05.

There are three different series:

  • Characteristic: slow, 3NW1 ...-0HG
    For the protection of control transformers, reactors, inductances. Significantly slower than the minimum requirements specified by UL for Class CC Fuses of 12 s at 2 × In.
  • Characteristic: quick 3NW2 ...-0HG
    For a wide range of applications, for the protection of lighting installations, heating, control systems
  • Characteristic: slow, current-limiting 3NW3 ...-0HG
    Slow for overloads and quick for short circuits. High current limitation for the protection of motor circuits.

Note:
For class CC compact fuse holders for motor starter combinations see: Fuse systems → Cylindrical fuse systems → Fuse holders in sizes 10 38 mm and Class CC.

Особенности

  • For switchgear assembly and machine manufacturers who export systems to the USA or Canada.
  • Easier export due to UL and CSA approvals for typical applications
  • Modern design with touch protection to BGV A3 ensures safe installation.
preloader

58230