preloader
mail@uselogic.ru  +7(495) 374 68 44 Заказать звонок

Область применения

  • Pumps
  • Compressors
  • Fans
  • Extruders
  • Motors in process systems
  • Branche Oil & Gas

Обзор

LOHER Motors with type of protection "e" (increase safety) distinguish themselves as the various components are optimally harmonized with one another (winding / rotor and components).
This is the reason that special construction regulations also apply for these motors.
When compared to motors with a flameproof enclosure, which makes any ignition non-hazardous, the protection philosophy for these motors is to avoid ignition, even when a fault situation occurs.
The permissible winding temperatures are reduced, which in turn results in a longer lifetime and a low risk of ignition.
Fault situation "locked rotor": LOHER Ex e motors set themselves apart as a result of the higher (than specified) safe locked rotor time - tE - this makes drive monitoring simpler, safer and uncritical.
"Increased safety" therefore also involves a longer service life and especially a higher degree of reliability and operational safety.

Особенности

  • Special demands are realized
    => electric motor design adapted to special requirements
  • Larger connection system
    => adapted to the existing electrical system
  • Parameter-optimized motors
    => result in high efficiencies and high power factor with a low noise level
  • In comparison to the standard and other Ex motors: Lower winding temperature limits
    => an even longer service life
  • Quality components are used
    => Extremely high operational reliability

Технические данные

Motors:

1PS2 (LOHER CHEMSTAR) Loher name: ENGV

Shaft heights:

Frame sizes 090 - 355 mm (area of standard motors)

Power range: 
(50 Hz types)

Up to 220 kW (thermally utilized according to temperature class B at TU = 40 °C)

Number of poles:

2 - 8 pole; also higher pole numbers for special versions
Pole changing2 speeds, e.g. 4/2, 6/4, 8/4, 8/6

Voltage range:

Low voltage up to 1000 V8

Rated voltages:

All of the usual low-voltages and voltage ranges according to IEC 60038.
However, also: Non-standard voltages and / or frequencies according to customer specifications.

Operating mode:

S1

Degree of protection:

IP55, IP56, to IP66

Cooling type:

IC 411

Type of construction:

IM B3
IM B5, IM B35, IM V1, IM V3, IM V5, IM V18, IM B14, IM B34 (special)

Enclosure:

Gray cast iron

Bearings:

Ball bearings

Standards:

IEC, EN, DIN, VDE

Types of protection:

"e" as well as dust explosion protection according to EN 50281-1-1 / EN 50281-1-2

Noise level:

All motors are noise-optimized (noise limit values according to EN 60034-9),
low-noise version possible for 2-pole motors (GG3)



Features

Options:

  • Regreasing system from FS 160 - SPM nipple from FS 132 - stainless steel screws/bolts - larger connection system
  • Additional terminal box from FS 132 - anti-condensation heating from FS 132 - condensation water drain from FS 132
  • PTC thermistor or Pt100 as additional protection (TMS)
  • Can also be supplied for 60 Hz (adapted winding - increased power rating)
  • All motors with insulating material class H
  • All motors are available with an electrical design according to "NEMA Standards Publication No MG1"
  • Flanged motors can be designed and implemented with flange and shaft end in accordance with NEMA

Special versions e.g. for:

  • Special shaft end, backstop, special paint finishes
  • Low temperatures down to -60 °C
  • Available in temperature class T4 and also for increased ambient temperatures
preloader