Degrees of protection

The EN 60529 standard covers the protection of electrical equipment by means of housings, covers or equivalent, and includes:

  • Protection of persons against accidental contact with live or moving parts within the housing and protection of the equipment against the ingress of solid foreign matter (touch protection and protection against ingress of solid foreign matter)
  • Protection of the equipment against the ingress of water (water protection)
  • Abbreviations for the internationally agreed degrees of protection

The degrees of protection are specified by abbreviations comprising the code letters IP and two digits.

Degree of protection

First digit

(touch protection and protection against ingress of solid foreign matter)

Second digit

(protection of the equipment against the ingress of water)

IP20

(Standard)

Protected against solid foreign matter
diameter ≥ 12.5 mm

No water protection

IP21

(Option M21)

Protected against solid foreign matter
diameter ≥ 12.5 mm

Protected against drip water

Vertically falling water drops shall not have a harmful effect.

IP23

(Option M23)

Protected against solid foreign matter
diameter ≥ 12.5 mm

Protected against spray water

Water sprayed on both sides of the vertical at an angle of up to 60° shall not have a harmful effect.



Cabinet Modules fulfill the criteria for degree of protection IP20 as standard. The other degrees of protection outlined here are available as an option.

Технические данные

Unless specified otherwise, the following technical specifications are valid for all the following components of the SINAMICS S120 Cabinet Modules.

Electrical data

Line voltages

380 … 480 V 3 AC, ±10 % (-15 % < 1 min)

Line system configurations

Isolated systems (IT systems)

Line frequency

47 ... 63 Hz

Output frequency

0 … 300 Hz (> 100/160 Hz, observe the derating)

Line power factor
Fundamental

Active Line Module

Adjustable (factory-set to cosφ = 1)

Efficiency

> 97.0 %

Control method

Vector/servo control with and without encoder or V/f control

Fixed speeds

15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET)

Skipped speed ranges

4, programmable

Braking operation

With regenerative feedback, or the use of an optional brake chopper and braking resistors

Mechanical data

Degree of protection

IP20 (higher degrees of protection up to IP23 optional)

Protection class

I acc. to EN 61800‑5‑1

Touch protection

EN 50274 / BGV A3 for the intended purpose

Cabinet system

Rittal TS 8, doors with double-barb lock, three-section base plates for cable entry

Paint finish

RAL 7035 (indoor requirements)

Cooling method

Forced air cooling AF to EN 60146‑1‑1

Ambient conditions

Storage 1)

Transport 1)

Operation

Ambient temperature

-25 ... +55 °C

-25 ... +70 °C
above -40 °C2) for 24 hours

0 ... +40 °C
to +50 °C see derating data

Relative humidity

(condensation not permissible)

5 ... 95 % 2)
Class 1K4 acc. to IEC 60721‑3‑1

5 ... 95 % at 40 °C
Class 2K3 acc. to IEC 60721‑3‑2

5 ... 95 % 2)
Class 3K3 acc. to IEC 60721‑3‑3

Environmental class/harmful chemical substances

Class 1C2
acc. to EN 60721‑3‑1

Class 2C2
acc. to EN 60721‑3‑2

Class 3C2
acc. to EN 60721‑3‑3

Organic/biological influences

Class 1B1
acc. to EN 60721‑3‑1

Class 2B1
acc. to EN 60721‑3‑2

Class 3B1
acc. to EN 60721‑3‑3

Degree of pollution

2 acc. to EN 61800‑5‑1

2 acc. to EN 61800‑5‑1

2 acc. to EN 61800‑5‑1

Installation altitude

Cabinet Modules, chassis format:
up to 2000 m above sea level, without derating, > 2000 m, see characteristic curves/derating data

Mechanical stability

Storage 1)

Transport 1)

Operation

Vibratory load

Class 1M1
acc. to EN 60721‑3‑1

Class 2M1
acc. to EN 60721‑3‑2

  • Deflection

1.5 mm at 5 ... 9 Hz

3.1 mm at 5 ... 9 Hz

0.075 mm at 10 ... 58 Hz

  • With option B70

1.0 mm at 2 ... 13.2 Hz

  • Acceleration

5 m/s² at > 9 ... 200 Hz

10 m/s² at > 9 ... 200 Hz

9.8 m/s² at > 58 ... 200 Hz

  • With option B70

6.8 m/s² at > 13.2 ... 100 Hz

Shock load

Class 1M1
acc. to EN 60721‑3‑1

Class 2M1
acc. to EN 60721‑3‑2

Class 3M1
acc. to EN 60721‑3‑3

  • Acceleration

40 m/s² at 22 ms

100 m/s² at 11 ms

100 m/s² at 11 ms

Compliance with standards

Conformances/approvals, according to

CE (EMC directive No. 2004/108/EC and low-voltage directive No. 2006/95/EC)

Radio interference suppression

SINAMICS drive converter systems are not designed for connection to the public grid (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment" (industrial line supplies). The equipment can cause electromagnetic interference when it is connected to the public network. However, if supplementary measures are taken (e.g. → line filter), it can also be operated in the "first environment".



1) In transport packaging.

2) Deviations with respect to the specified class are underlined.

The most important directives and standards are listed below. These are used as basis for the SINAMICS S120 Cabinet Modules and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.

European directives

2006/42/EC

Machinery directive:
Legal guidelines of the EU member states for machines

2006/95/EC

Low-voltage directive:
Legal guidelines of the EU member states concerning electrical equipment for use within specified voltage limits

2004/108/EC

EMC directive:
Legal guidelines of the EU member states for electromagnetic compatibility

European standards

EN ISO 13849‑1

Safety of machinery – safety-related parts of control systems – Part 1: General design principles

EN 60146‑1‑1

Semiconductor converters – General requirements and line-commutated converters
Part 1-1: Specification of basic requirements

EN 60204‑1

Safety of machinery – Electrical equipment of machines
Part 1: General requirements

EN 60529

Degrees of protection provided by enclosures (IP code)

EN 61800‑2

Adjustable speed electrical power drive systems
Part 2: General requirements – Rating specifications for low-voltage adjustable frequency a.c. power drive systems

EN 61800‑3

Adjustable speed electrical power drive systems
Part 3: EMC requirements including specific test methods

EN 61800‑5‑1

Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements

EN 60204‑32

Safety of machinery – Electrical equipment of machines
Part 32: Requirements placed on cranes and lifting equipment

EN 50274/BGV A3

Information technology – Installation of communication cables 
Part 3: Installation planning and installation practice outdoors

EN 60664‑1

Insulation coordination for equipment within low-voltage systems 
Part 1: Principles, requirements and tests

EN 61346-2

Reference marking for technical products and technical product documentation

IEC 60721-3-1

Classification of environmental conditions 
Part 3: Classification of groups of environmental parameters and their severities;
section 1: Long-term storage

IEC 60721-3-2

Classification of environmental conditions 
Part 3: Classification of groups of environmental parameters and their severities;
section 2: Transportation

IEC 60721-3-3

Classification of environmental conditions 
Part 3: Classification of groups of environmental parameters and their severities;
section 3: Stationary use at weather-protected locations



preloader

55935